Skip to main content
Siemens 3VA2125-6HL36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-6HL36-0AA0 SENTRON MCCB, 25 A, 3-Pole, ETU32

MPN3VA2125-6HL36-0AA0
Active

Siemens SENTRON 3VA2125-6HL36-0AA0, molded case circuit breaker, 3-pole, 25 A rated continuous current, ETU320 electronic overcurrent release, interrupting ratings 242 kA at 240 V down to 3.7 kA at 690 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2125-6HL36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2125-6HL36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classH
Breaking capacity at 240 V242 kA
Breaking capacity at 415 V187 kA
Breaking capacity at 440 V187 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V3.7 kA
Power loss, max.0.6 W
3VA2125-6HL36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU320
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2125-6HL36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typedouble-sided box terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2125-6HL36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2125-6HL36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2125-6HL36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

Rated 25 A continuous current with a 3-pole configuration, it carries the ETU320 electronic overcurrent release — a microprocessor-based trip unit that provides adjustable overload and short-circuit protection curves, unlike fixed thermal-magnetic breakers. The interrupting capacity reaches 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V, so it handles high-fault scenarios typical of industrial main feeders or large branch circuits.

Dimensions are 105 mm wide, 181 mm high, 86 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling. Operating temperature range is -25 °C to 70 °C, with storage from -40 °C to 80 °C, so it can sit in unheated warehouses or hot machine cabinets.

Frequently asked questions

Will 3VA2125-6HL36-0AA0 drop into a panel specified around 3VA2125-8KQ42-0AA0 without rewiring?

Yes — both share the same 3-pole frame, 25 A rating, and physical dimensions (105 mm wide, 181 mm high, 86 mm deep). The difference is the trip unit: the 6HL36 uses the ETU320, while the 8KQ42 carries a different electronic release. No rewiring or enclosure modification is needed for a direct swap.

MPN
3VA2125-6HL36-0AA0