Siemens 3VA2140-0KQ32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2140-0KQ32-0AA0 SENTRON MCCB, 40 A, 440 kA at 415

MPN3VA2140-0KQ32-0AA0
Active

Siemens SENTRON 3VA2140-0KQ32-0AA0, molded case circuit breaker, line protection, 3-pole, 40 A rated continuous current, ETU860 electronic trip unit, 440 kA breaking capacity at 415 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2140-0KQ32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2140-0KQ32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classE
Breaking capacity at 415 V440 kA
Breaking capacity at 690 V187 kA
Power loss, max.1.2 W
3VA2140-0KQ32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU860
Overcurrent protection functionLSIG
Ground-fault monitoringSummation current formation L-conductor
Grounding protection functionYes
3VA2140-0KQ32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2140-0KQ32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionYes
Motor drive optionYes
Auxiliary CO contacts0
3VA2140-0KQ32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2140-0KQ32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

What this MCCB does on the line

The 3VA2140-0KQ32-0AA0 measures 105 mm wide by 181 mm tall by 86 mm deep — a standard 3-pole MCCB footprint for Siemens SENTRON 3VA2 frames.

Trip unit and protection features

The ETU860 electronic trip unit supports communication (via the integrated communication function) and ground-fault monitoring using summation current formation on the L-conductor. The N-conductor protection is adjustable from OFF to 40%–160% of the rated current, giving flexibility for 3-phase + N applications.

Frequently asked questions

What is the breaking capacity of 3VA2140-0KQ32-0AA0 at 415 V?

440 kA at 415 V, and 187 kA at 690 V.

What trip unit does this MCCB use?

The ETU860 electronic trip unit with adjustable long-time, short-time, instantaneous, and ground-fault protection, plus communication capability.

Where can I buy 3VA2140-0KQ32-0AA0 and how is it quoted?

It is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — no stock figures are published here.