The Siemens 3VA4112-6ED34-0AA0 is a 3-pole SENTRON molded-case circuit breaker rated 125 A at 40 °C, with a TM210 thermal-magnetic release designed for system protection — meaning it handles distribution feeder duty, not motor-starting curves. That 65 kA at 480 Y/277 V tells you it's rated for wye-grounded systems common in North American commercial panels. Thermal derating is published across the full range: 125 A at 40 °C, 120 A at 50 °C, 115 A at 60 °C, 109 A at 70 °C. Dimensions are 75.1 mm deep, 76.2 mm wide, 129.4 mm high — a standard 3-pole MCCB footprint that drops onto DIN rail or direct-mount busbars.
Siemens 3VA4112-6ED34-0AA0 SENTRON MCCB, 125 A, 3-Pole, 100
MPN3VA4112-6ED34-0AA0
Active
Siemens SENTRON 3VA molded-case circuit breaker, 3VA4112-6ED34-0AA0, 3-pole, 125 A at 40 °C, TM210 thermal-magnetic release, 100 kA at 240 V AC, system protection design.
$265.43Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded-case circuit breaker |
| Brand / range | SENTRON |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Current at 40 °C | 125 A |
| Current at 45 °C | 12 A |
| Current at 50 °C | 120 A |
| Current at 55 °C | 117 A |
| Current at 60 °C | 115 A |
| Current at 65 °C | 112 A |
| Current at 70 °C | 109 A |
| Switching capacity class | H |
| Breaking capacity at 240 V | 100 kA |
| Power loss, max. | 29.1 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | Infeed side: Low tab |
| Main circuit connector arrangement | output side: circular conductor connection |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | No |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 15 000 |
| Height | 129.4 mm |
| Width | 76.2 mm |
| Depth | 75.1 mm |
| Height (in) | 5.09 in |
| Width (in) | 3 in |
| Depth (in) | 2.96 in |
Product details
Frequently asked questions
Where can I buy 3VA4112-6ED34-0AA0 and get a price?
This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.
What interrupting capacity does this breaker have at 480 V?
The 3VA4112-6ED34-0AA0 is rated 65 kA at 480 V AC and 65 kA at 480 Y/277 V, with 25 kA at 600 Y/347 V.
What is the thermal derating at 60 °C?
At 60 °C the continuous current rating derates to 115 A; at 70 °C it drops to 109 A.