Skip to main content
Siemens 3VA4150-6ED34-1AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA4150-6ED34-1AA0 MCCB, 50 A, 100 kA at 240

MPN3VA4150-6ED34-1AA0
Active

Siemens SENTRON 3VA series, molded-case circuit breaker, 3-pole, 50 A rated, 100 kA at 240 V, 65 kA at 480 V, TM210 release, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4150-6ED34-1AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
Product versionSystem protection
3VA4150-6ED34-1AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C50 A
Current at 45 °C50 A
Current at 50 °C50 A
Current at 55 °C49 A
Current at 60 °C47 A
Current at 65 °C46 A
Current at 70 °C44 A
Switching capacity classH
Breaking capacity at 240 V100 kA
Power loss, max.9.7 W
3VA4150-6ED34-1AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA4150-6ED34-1AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Main circuit connector arrangementLoad side: Circular conductor terminal
Protection class (IP), frontIP40
3VA4150-6ED34-1AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4150-6ED34-1AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4150-6ED34-1AA0 — Mechanical
ParameterValue
Height129.4 mm
Width76.2 mm
Depth75.1 mm
Height (in)5.1 in
Width (in)3 in
Depth (in)3 in

Product details

What this 3VA frame carries

The Siemens SENTRON 3VA4150-6ED34-1AA0 is a 3-pole molded-case circuit breaker rated 50 A continuous at 40 °C through 50 °C, with the TM210 thermal-magnetic release. Instantaneous pickup is fixed at 500 A (10× In), so it clears bolted faults fast but won't nuisance-trip on motor inrush on a properly sized feeder. It's meant for distribution panel main or feeder duty — not for direct motor switching. The TM210 release gives you thermal adjustment via a dial on the front, but the magnetic is non-adjustable at 500 A.

Above that it steps down: 49 A at 55 °C, 47 A at 60 °C, 46 A at 65 °C, 44 A at 70 °C. If your panel internal ambient runs hot — say next to a drive or transformer — size the breaker for the derated number, not the nameplate 50 A.

Footprint is 76.2 mm wide × 129.4 mm tall × 75.1 mm deep — a standard 3-inch wide MCCB form factor. It mounts to a DIN rail or panel via the rear slots. Power loss runs 9.7 W max at rated load — negligible for thermal panel design unless you're packing a dozen of these in a small enclosure.

Frequently asked questions

What is the interrupting rating of this breaker at 480 V?

65 kA at 480 V, and 100 kA at 240 V. At 600Y/347 V it drops to 25 kA.

What is the adjustable instantaneous pickup range?

Fixed at 500 A — the TM210 release has a non-adjustable magnetic trip set at 10× In. Only the thermal element is adjustable via the front dial.

Where can I buy the 3VA4150-6ED34-1AA0 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm quote.

What compliance documentation is available for this MCCB?

The breaker carries UL file HEAM and is designed to IEC 81346-2 (reference code Q). Typical Siemens SENTRON documentation includes RoHS and REACH declarations; consult the product documentation for specific certificate versions.

MPN
3VA4150-6ED34-1AA0