Skip to main content
Siemens 3VM1025-3ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1025-3ED32-0AA0 SENTRON MCCB, 25 A, 3-Pole, TM210

MPN3VM1025-3ED32-0AA0
Active

Siemens SENTRON 3VM1025-3ED32-0AA0, 3-pole molded case circuit breaker, TM210 thermal-magnetic release, rated 25 A at 40 °C, interrupting capacity 76 kA at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1025-3ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1025-3ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C24 A
Current at 60 °C24 A
Current at 65 °C23 A
Current at 70 °C23 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V8 kA
Power loss, max.9 W
3VM1025-3ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1025-3ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1025-3ED32-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1025-3ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1025-3ED32-0AA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.1 in
Width (in)3 in
Depth (in)2.8 in

Product details

Rated at 25 A continuously at 40 °C, it holds that full rating through 50 °C, then derates to 24 A at 55–60 °C and 23 A at 65–70 °C — useful to know if the panel runs hot near a drive or transformer.

Interrupting capacity — voltage-dependent, not a single number

The 76 kA at 240 V is the headline figure, but the real-world SCCR drops sharply as system voltage rises: 53 kA at 415 V, 32 kA at 440 V, and 8 kA at 500 V. Rated insulation voltage Ui is 690 V, and max DC operational voltage is 500 V.

Lifecycle stage is marked as current — meaning Siemens still lists it as an active catalog number with no announced end-of-life or last-time-buy window.

No communication function, no motor drive option, no neutral conductor upgrade path. The 3-pole width is the standard 3-inch (76.2 mm) MCCB footprint — drops into a panel lugged for a 3-pole SENTRON frame without re-drilling the mounting plate.

Frequently asked questions

Does the 3VM1025-3ED32-0AA0 include a ground-fault monitoring function?

No, it is specified without ground-fault monitoring. The TM210 release provides LI (long-time and instantaneous) protection only.

MPN
3VM1025-3ED32-0AA0