The Siemens SENTRON 3VM1032-3ED42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 32 A continuous at 40 °C, with a TM210 thermal-magnetic release designed for line protection. Its interrupting capacity reaches 76 kA at 240 VAC, 53 kA at 415 VAC, 32 kA at 440 VAC, and 8 kA at 500 VAC — meaning it can safely clear fault currents up to those levels without upstream cascading, which is the key figure for panel SCCR coordination.
Dimensions & Panel Fit
Thermal Derating & Operating Range
Rated current holds at 32 A from 40 °C through 50 °C, then derates to 31 A at 55–60 °C and 30 A at 65–70 °C.