Skip to main content
Siemens 3VM1032-4ED32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1032-4ED32-0AA0 SENTRON MCCB, 320A, 3-Pole, TM210

MPN3VM1032-4ED32-0AA0
Active

Siemens SENTRON molded case circuit breaker, 3VM1032-4ED32-0AA0, 3-pole, 320 A, TM210 thermal-magnetic release, interrupting capacity 121 kA at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1032-4ED32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VM1032-4ED32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V40 kA
Breaking capacity at 500 V12 kA
Power loss, max.11 W
3VM1032-4ED32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VM1032-4ED32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1032-4ED32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1032-4ED32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1032-4ED32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.12 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

SENTRON 3VM1032-4ED32-0AA0 — 320 A MCCB for line protection

Interrupting capacity varies with system voltage: 121 kA at 240 V AC, 76 kA at 415 V, 40 kA at 440 V, and 12 kA at 500 V. That spread covers common industrial voltages from low-voltage switchgear to 480 V distribution. Current rating holds at 32 A from 40 °C through 50 °C, then derates to 31 A at 55 °C and 60 °C, and 30 A at 65 °C and 70 °C.

Power loss is 11 W maximum at rated load. In a densely packed panel, that heat must be considered in the thermal budget — it is modest for a 320 A frame but not negligible in a sealed enclosure with multiple breakers. The breaker has no undervoltage release, no trip indicator, no voltage trigger, no communication function, and no ground-fault monitoring. It is a straight thermal-magnetic line-protection device — no auxiliary electronics to fail or configure. If you need remote signaling or undervoltage protection, you will add external accessories or step to a different variant.

Frequently asked questions

What is the interrupting capacity of this MCCB at 415 V?

76 kA at 415 V AC. At 240 V it is 121 kA, at 440 V it is 40 kA, and at 500 V it is 12 kA.

Where can I buy 3VM1032-4ED32-0AA0 and how is it quoted?

We source this part through Siemens distribution and quote it to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3VM1032-4ED32-0AA0