The 3VM1032-2ED42-0AA0: Rated 32 A continuous at 40 °C (derated to 30 A at 70 °C), so this MCCB carries a 32 A bus or feeder without nuisance tripping in a ventilated enclosure. Breaking capacity steps down with system voltage: 53 kA at 240 V, 32 kA at 415 V, 14 kA at 440 V, 8 kA at 500 V. The TM210 overcurrent release is a fixed thermal-magnetic unit with an adjustable magnetic trip (li max. 320 A). Thermal element protects against overload; magnetic element clears short-circuits.
Physical integration
The 4-pole width (101.6 mm) occupies roughly four 1-inch module spaces — verify gland-plate clearance and adjacent device fill factor before committing the layout. IP40 on the front face means tools-only access; no washdown rating, so keep this behind a locked panel door in wet environments.
Rated insulation voltage Ui of 690 V AC, with a max DC operational voltage of 500 V. The manufacturer provides RoHS and REACH declarations; UL and IEC certification are standard for the SENTRON series. No ground-fault monitoring or N-conductor protection built in — specify external GFCI if required.