Skip to main content
Siemens 3VM1120-3EE46-0AA2 — Molded Case Circuit Breakers (MCCB)

SENTRON 3VM1120-3EE46-0AA2 4-Pole MCCB, 20A, 76kA at 240V

MPN3VM1120-3EE46-0AA2

SENTRON 3VM1120-3EE46-0AA2, 4-pole molded case circuit breaker, 20 A rated continuous current, TM220 thermal-magnetic release, N switching capacity class, 76 kA at 240 V AC, 53 kA at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1120-3EE46-0AA2 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1120-3EE46-0AA2 — Ratings
ParameterValue
Number of poles4
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C19 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Power loss, max.12 W
3VM1120-3EE46-0AA2 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
3VM1120-3EE46-0AA2 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1120-3EE46-0AA2 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1120-3EE46-0AA2 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Product details

The SENTRON 3VM1120-3EE46-0AA2 is a 4-pole molded case circuit breaker (MCCB) rated for 20 A continuous current across the 40 °C to 55 °C ambient range, with only a 1 A derating step at 60 °C. That thermal stability means it holds its full rating in a warm enclosure without oversizing the frame — useful when the panel sits near a motor or drive. The interrupting capacity tells the real story for fault coordination: 76 kA at 240 V AC, 53 kA at 415 V AC, 32 kA at 440 V AC, and 11.9 kA at 500 V AC. The N switching capacity class means this breaker is designed for normal-duty industrial distribution — not the high-stress utility tie or large motor branch that demands the S class. For most panelboard and sub-distribution applications, the N class provides the right balance of fault-clearing muscle without paying for a frame you don't need. The TM220 overcurrent release is a thermal-magnetic type — thermal element for overload protection, magnetic trip for short-circuit. The LI protective function confirms it provides long-time delay and instantaneous protection, no electronic adjustment. That makes it a straightforward drop-in for standard feeder or branch protection where you don't need the selectivity tuning of an electronic trip unit.

The main current circuit uses box terminals with front connection — standard for panelboard and switchboard mounting. The frame size is rated for up to 160 A, so this 20 A breaker sits in a physically larger frame than its continuous rating suggests. That's typical for the 3VM platform: the frame is sized for the interrupting capacity, not the amp rating. Verify the mounting footprint against your existing bus bar or DIN-rail adapter before committing the panel layout. Front IP40 protection. No motor drive option and no auxiliary contacts from the factory.

Environmental limits and power loss

Maximum power loss 12 W.

Frequently asked questions

What type of overcurrent release does this MCCB use?

The TM220 is a thermal-magnetic release providing LI protection — long-time delay for overloads and instantaneous magnetic trip for short-circuits. No electronic adjustment or ground fault monitoring is included.

MPN
3VM1120-3EE46-0AA2