Skip to main content
Siemens 3VM1132-3GE42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1132-3GE42-0AA0 SENTRON MCCB, 4-pole, 32 A, 76 kA

MPN3VM1132-3GE42-0AA0
Active

Siemens SENTRON 3VM1132-3GE42-0AA0, 4-pole molded case circuit breaker, 32 A rated at 40 °C, 76 kA interrupting at 240 V, TM220 release, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1132-3GE42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VM1132-3GE42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V12 kA
Power loss, max.11 W
3VM1132-3GE42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VM1132-3GE42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1132-3GE42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1132-3GE42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1132-3GE42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

SENTRON 3VM1132-3GE42-0AA0 — 4-pole MCCB, 32 A, 76 kA at 240 V

The Siemens SENTRON 3VM1132-3GE42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated 32 A at 40 °C with a TM220 thermal-magnetic overcurrent release, designed for line protection in distribution panels. Its interrupting capacity reaches 76 kA at 240 V, 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V — covering most industrial low-voltage fault levels. The 70 mm depth and 101.6 mm width fit standard MCCB mounting footprints; IP40 on the front suits enclosed panel installation.

Thermal derating and continuous current

Rated current holds at 32 A from 40 °C through 50 °C, then steps down to 31 A at 55 °C and 60 °C, and 30 A at 65 °C and 70 °C. The TM220 release handles minimum loads down to 1 A, so it can protect lightly loaded branch circuits without nuisance tripping.

Integration notes

Four-pole design with 100% N-conductor protection. Insulation voltage rated 800 V. Power loss 11 W maximum. Ground-fault monitoring version is without. Mounts in standard panel cutouts for SENTRON 3VM frame breakers; verify busbar and lug kit compatibility with the specific distribution board.

MPN
3VM1132-3GE42-0AA0