It carries 50 A continuously at 40 °C ambient, with a slight derating curve: 49 A at 55 °C, 48 A at 60 °C, 46 A at 65 °C, and 45 A at 70 °C. Interrupting capacity is specified per voltage: 121 kA at 240 V AC, 76 kA at 415 V AC, 53 kA at 440 V AC, and 12 kA at 500 V AC. The insulation voltage rating is 800 V. For DC switching capacity values, the manufacturer directs to the 3VA Molded Case Circuit Breaker Manual.
Maximum power loss is 15 W.