Siemens 4EU2722-0AN00-4BA0 — Line/Load Reactors

Siemens 4EU2722-0AN00-4BA0 Commutating Choke, 95A Rated, 400

MPN4EU2722-0AN00-4BA0

Siemens 4EU2722-0AN00-4BA0 commutating choke for converter duty, 3-phase, 400V AC, 95A rated current (105A max), 0.2 mH, IP00, thermal class H.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU2722-0AN00-4BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.0002H
Relative inductive voltage drop2.86%
4EU2722-0AN00-4BA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU2722-0AN00-4BA0 — Electrical
ParameterValue
Rated operating voltage400V
Number of phases3
Rated current (DC)128.6A
Voltage typeAC
Rated operating frequency50Hz
4EU2722-0AN00-4BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)169W
Power loss, iron core (W)99W
Rated ambient temperature40°C
4EU2722-0AN00-4BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU2722-0AN00-4BA0 — Mechanical
ParameterValue
Main-circuit connection typefree cable endings
IP protection ratingIP00
Height0.248m
Width0.27m
Depth0.187m

Product details

The Siemens 4EU2722-0AN00-4BA0 is a 3-phase commutating choke for converter input. It operates at 400 V AC, 95 A rated current, 105 A maximum. A 2.86% drop is a standard value for a line reactor — it provides meaningful harmonic attenuation without dropping so much voltage that the drive's DC bus undervoltages under load.

Where it fits — panel and thermal considerations

This is an open-frame (IP00) component. Dimensions are 0.27 m wide, 0.248 m high, 0.187 m deep. Thermal class H insulation per IEC 60085 means the winding can withstand a 180 °C hot-spot temperature. The total power loss is the sum of the coil loss (169 W) and the iron-core loss (99 W), so 268 W must be dissipated inside the panel. That is a significant heat load — forced ventilation or a properly sized cabinet is required to keep the ambient temperature at or below the 40 °C rating. The main circuit connection is via free cable endings, so the installer provides the ring terminals or ferrules. This is typical for a choke of this class — no pre-made connector, just stripped and tinned leads that land on a terminal block or the converter's input terminals.

Frequently asked questions

What compliance documentation does Siemens provide for 4EU2722-0AN00-4BA0?

The product is designed to EN 61558-2-20, the standard for chokes and reactors. Standard Siemens documentation includes a CE declaration of conformity and a datasheet. RoHS and REACH compliance information is available on request.