Siemens 4EU3021-0AA10-0AA0 — Line/Load Reactors

Siemens 4EU3021-0AA10-0AA0 Commutating Choke, 547A, 50Hz

MPN4EU3021-0AA10-0AA0

Siemens SENTRON 4EU3021-0AA10-0AA0, commutating choke for converter, 3-phase, 290 V AC, 547 A max, 492.3 A rated, IP00, flat-type terminal.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3021-0AA10-0AA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000025H
Relative inductive voltage drop2.62%
4EU3021-0AA10-0AA0 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU3021-0AA10-0AA0 — Electrical
ParameterValue
Rated operating voltage290V
Number of phases3
Rated current (DC)670.3A
Voltage typeAC
Rated operating frequency50Hz
4EU3021-0AA10-0AA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)230W
Power loss, iron core (W)80W
Rated ambient temperature40°C
4EU3021-0AA10-0AA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3021-0AA10-0AA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.269m
Width0.3m
Depth0.211m

Product details

What this choke is and where it runs

It carries a maximum continuous current of 547 A and a rated current of 492.3 A, with an inductance of 0.000025 H (25 µH) and a relative inductive voltage drop of 2.62% at rated conditions. That 2.62% drop is a typical value for a line reactor sized to limit harmonic distortion and di/dt stress on the converter's input rectifier — not a tuning choke for a drive output, but a line-side smoothing element.

Thermal and environmental limits

Thermal class H (IEC 60085) means the coil insulation withstands 180 °C hot-spot temperature — essential for a choke pulling 230 W of copper loss plus 80 W of iron-core loss at rated load. The ambient temperature rating of 40 °C is the reference; above that the current must be derated per the manufacturer's curve, which is typical for any IP00, open-frame reactor. IP00 means no ingress protection — this choke belongs in a clean, dry, ventilated enclosure, not on a washdown line or outdoors.

Physical fit and connection

Dimensions are 0.3 m wide × 0.269 m high × 0.211 m deep — roughly the footprint of a small suitcase. The main current circuit uses flat-type terminals (bus-bar or cable-lug connection), not screw-clamp or spring-cage. That means the panel builder needs to plan for bolted connections with appropriate lug size and torque, not a DIN-rail terminal block. The choke is not designed for snap-on DIN mounting; it is a chassis-mount or bolted-to-subplate component.

Standard compliance

The design follows EN 61558-2-20, the safety standard for small transformers and chokes. That covers dielectric strength, creepage distances, and thermal endurance. No UL or CSA listing is stated in the evidence, so for North American installs the integrator should verify local code acceptance or request the UL-recognized variant.

MPN
4EU3021-0AA10-0AA0