Skip to main content
Siemens 4EU3622-0EC00-1BA0 — Line/Load Reactors

Siemens 4EU3622-0EC00-1BA0 Mains Choke, 871A, 480V, 3-Phase

MPN4EU3622-0EC00-1BA0

Siemens SENTRON 4EU3622-0EC00-1BA0 mains choke (line reactor) for variable-frequency drives, 3-phase, 480V AC, rated 784A (max 871A), 0.019mH, 1.6% voltage drop, IP00, flat-type terminals, UL/CSA recognized.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU3622-0EC00-1BA0 — Inductance & Impedance
ParameterValue
Rated inductance0.000019H
Relative inductive voltage drop1.6%
4EU3622-0EC00-1BA0 — Identification
ParameterValue
Product designationNetzdrossel f. FU
4EU3622-0EC00-1BA0 — Electrical
ParameterValue
Rated operating voltage480V
Number of phases3
Voltage typeAC
Rated operating frequency47Hz
4EU3622-0EC00-1BA0 — Losses & Thermal
ParameterValue
Power loss, coil (W)268.9W
Power loss, iron core (W)189.4W
Rated ambient temperature50°C
4EU3622-0EC00-1BA0 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU3622-0EC00-1BA0 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.321m
Width0.35m
Depth0.237m

Product details

What this mains choke does for the drive line

The Siemens 4EU3622-0EC00-1BA0 is a three-phase mains choke (line reactor) for the input side of a variable-frequency drive. Rated 784 A continuous with a 871 A maximum at 47 Hz.

Rated current 784 A at 480 V AC, 3-phase, 47 Hz — thermal continuous rating at 50 °C ambient. The 871 A maximum figure reflects the short-time overload capability. Power loss splits into coil loss 268.9 W and iron-core loss 189.4 W — total roughly 458 W dissipated as heat. That heat stays inside the enclosure; IP00 means no housing, so the choke must be mounted in a clean, dry, ventilated cabinet (or a dedicated electrical room). Class H insulation (180 °C thermal class per IEC 60085) gives a generous temperature margin for high-ambient or overload conditions.

The choke measures 0.35 m wide × 0.321 m tall × 0.237 m deep — a substantial block, not a DIN-rail component. Main circuit connections are flat-type terminals (bus-bar or cable-lug interface), typical for high-current line reactors. Plan for rigid bus work or large-gauge cable lugs; the terminals expect a bolted connection, not a spring clamp.

The lifecycle stage is recorded as mature — meaning it's an established, stable design with no active phase-out notice. It carries UL/CSA recognition per EN 61558, so it's accepted for North American panels that require listed components. The IP00 protection class means no ingress protection; install in a cabinet that keeps out dust and moisture.

Frequently asked questions

What is the voltage drop of this line reactor?

The relative inductive voltage drop is 1.6 % at rated current, voltage, and frequency — a typical value for a line reactor sized to limit harmonics without excessive voltage sag under load.

What compliance documentation does this choke carry?

The choke is UL/CSA recognized and designed to EN 61558. For RoHS, REACH, or specific declaration of conformity, request those documents with your RFQ.

MPN
4EU3622-0EC00-1BA0