Skip to main content
Siemens 4EU5021-0AC00 — Line/Load Reactors

Siemens 4EU5021-0AC00 Commutating Choke, 617A 3-Phase 380V

MPN4EU5021-0AC00

Siemens SENTRON 4EU5021-0AC00 commutating choke for converter, 3-phase, 380V AC, 617A rated current, 50Hz, IP00, Class H insulation, flat-type terminals.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

4EU5021-0AC00 — Inductance & Impedance
ParameterValue
Rated inductance0.00018H
Relative inductive voltage drop15.62%
4EU5021-0AC00 — Identification
ParameterValue
Product designationKommut.-Drossel f. Stromrichter
4EU5021-0AC00 — Electrical
ParameterValue
Rated operating voltage380V
Number of phases3
Rated current (DC)756.1A
Voltage typeAC
Rated operating frequency50Hz
4EU5021-0AC00 — Losses & Thermal
ParameterValue
Power loss, coil (W)1 310W
Power loss, iron core (W)345W
Rated ambient temperature40°C
4EU5021-0AC00 — Approvals
ParameterValue
Thermal class (IEC 60085)H
4EU5021-0AC00 — Mechanical
ParameterValue
Main-circuit connection typeflat connector
IP protection ratingIP00
Height0.565m
Width0.518m
Depth0.318m

Product details

Commutating choke for converter duty

The Siemens 4EU5021-0AC00 is a 3-phase commutating choke (line reactor) rated for 617 A continuous at 380 V AC, 50 Hz. It is designed for converter input circuits where it limits di/dt, reduces harmonics, and protects the rectifier from line notching and commutation notches. The 0.00018 H inductance per phase and 15.62 % relative inductive voltage drop define its impedance — this is the figure that governs how much fault current the choke limits and how much voltage sag the DC link sees under load.

Rated 617 A AC continuous, the choke is sized for the input of a converter driving a motor load drawing roughly that line current — think a 315–355 kW drive on 400 V class supply. The DC rating of 756.1 A tells you the choke can handle the higher RMS current in DC-link applications if repurposed, but the primary role is AC line-side. The 1310 W coil loss and 345 W iron loss sum to about 1.65 kW of heat that must be ventilated out of the enclosure; IP00 means no ingress protection — the choke is an open-frame component that goes inside a panel or cabinet, never in a washdown or dusty zone. Class H insulation (180 °C rated) gives thermal headroom for the 40 °C ambient rating, so it can sit in a warm cabinet without derating.

Physical footprint and connections

Dimensions: 0.518 m wide × 0.565 m high × 0.318 m deep — a substantial block that needs a floor-mount or heavy shelf in the panel, not a DIN rail. Main circuit connections are flat-type terminals (bus-bar compatible), not screw clamps; plan for bolted copper bars or braided straps rated for the full 617 A. The three phases enter and exit on the same terminal plane, so layout the bus work accordingly.

Frequently asked questions

What are the key ratings for 4EU5021-0AC00?

Rated 617 A continuous at 380 V AC, 3-phase, 50 Hz. Inductance 0.00018 H per phase, relative inductive voltage drop 15.62 %. DC rating 756.1 A. Class H insulation, IP00 open-frame design.

Where can I buy 4EU5021-0AC00 and get current pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What are the physical dimensions of 4EU5021-0AC00?

Width 0.518 m, height 0.565 m, depth 0.318 m. Flat-type terminals for main circuit connection. Not a DIN-rail mount; requires floor or shelf mounting in the panel.

MPN
4EU5021-0AC00