Siemens 5SL6232-7BB — 2-Pole MCB (DIN Rail)

Siemens 5SL6232-7BB SENTRON MCB, 2-Pole C-Curve 32 A, 6 kA

MPN5SL6232-7BB

Siemens SENTRON 5SL6232-7BB, 2-pole miniature circuit breaker, C-curve, 32 A rated at 400 V AC, 6 kA breaking capacity per EN 60898 and IEC 60947-2, 2 modular width units.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL6232-7BB — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentResidential buildings/infrastructure
5SL6232-7BB — Electrical
ParameterValue
Number of poles2
Supply voltage at AC rated value400 V
5SL6232-7BB — Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SL6232-7BB — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SL6232-7BB — Environmental
ParameterValue
Pollution degree2
At 30 °C rated value32 A
5SL6232-7BB — Specifications
ParameterValue
At AC rated value32 A
According to EN 60898 rated value6 kA
Energy Limitation Class3

Product details

What the ratings mean for fit

The Siemens 5SL6232-7BB is a 2-pole miniature circuit breaker from the SENTRON series, rated 32 A at 400 V AC with a C tripping characteristic. The C-curve means it trips between 5 and 10 times rated current — suited for inductive loads like small motors or lighting banks where inrush is moderate, not for high-surge transformer primaries (that would call for a D-curve). Breaking capacity is 6 kA per both EN 60898 and IEC 60947-2 — that is the maximum prospective fault current the breaker can safely interrupt at 400 V AC. For a residential or light-commercial distribution board fed by a transformer with a known fault level under 6 kA, this holds. If the available fault current at the panel exceeds 6 kA, you need a higher-rated breaker or a current-limiting upstream device. Temperature derating is published: 32 A at 30 °C, 29.56 A at 40 °C, 28.16 A at 45 °C, 25.48 A at 55 °C. If the breaker sits in a warm enclosure — near other heat sources or in a non-ventilated panel — use the 40 °C or 55 °C column to size the load. The 2.3 W power loss per pole at rated current adds up; 4.6 W total for the two poles needs to be dissipated inside the enclosure.

Mounting and integration

Width is 36 mm (2 modular units), depth 76 mm, installation depth 70 mm. Mounts on a standard DIN rail in any position — vertical, horizontal, or flat — per the any-position rating. IP20 with connected conductors means it is protected against finger contact but not against moisture; keep it inside a closed panel or enclosure rated for the environment. Sealable — the breaker accepts a seal or lock to prevent unauthorized toggling, useful for safety circuits or critical loads. Supplementary devices (auxiliary contacts, shunt trips, alarm switches) are installable, so you can add remote status or trip indication without replacing the breaker.

Frequently asked questions

What is the breaking capacity of 5SL6232-7BB?

6 kA per EN 60898 and IEC 60947-2 at 400 V AC. That is the maximum fault current it can safely interrupt under those standards.

What is the temperature derating for 5SL6232-7BB?

Rated 32 A at 30 °C, 29.56 A at 40 °C, 28.16 A at 45 °C, and 25.48 A at 55 °C. Use the 40 °C or 55 °C column for warm enclosure installations.

Where can I buy 5SL6232-7BB?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit a request for a firm quote.