Skip to main content
Siemens 5SL6532-6 — 1-Pole MCB (DIN Rail)

Siemens 5SL6532-6 SENTRON MCB, B-Curve, 32 A, 230 V, 6 kA

MPN5SL6532-6
Active

Siemens SENTRON 5SL6532-6 miniature circuit breaker, 1P+N, B-curve, 32 A, 230 V AC, 6 kA breaking capacity, 2 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6532-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityResidential buildings/infrastructure
5SL6532-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Energy limitation class3
Overvoltage categoryIII
5SL6532-6 — Mounting & Connection
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6532-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL6532-6 is a SENTRON miniature circuit breaker — 1P+N pole configuration, B tripping characteristic, rated 32 A at 230 V AC. It breaks fault currents up to 6 kA per both EN 60898 and IEC 60947-2, so it handles the standard residential and light commercial short-circuit duty without needing an upstream fuse. Rated for ambient temps from -40 °C to 75 °C, overvoltage category III, pollution degree 2 — typical for a distribution board environment.

Sealable with a lead or wire seal — useful for utility or rental-metering applications where tamper evidence is required. Halogen-free and silicon-free construction, so it won't outgas corrosive compounds in enclosed or sensitive environments. IP20 with connected conductors; fine for a dry indoor distribution board, not for washdown.

Frequently asked questions

What is the breaking capacity of 5SL6532-6?

6 kA per EN 60898 and IEC 60947-2 at 230 V AC.

Will 5SL6532-6 drop into a panel that was specified around 5SL6120-7 without rewiring?

No — the 5SL6120-7 is a single-pole (1P) unit at 18 mm width, while the 5SL6532-6 is 1P+N at 36 mm. The wider footprint and the neutral pole mean the panel's DIN-rail allocation and wiring need adjustment.

Where can I buy 5SL6532-6?

Sourced and quoted to order against an RFQ through independent distribution; current pricing and availability confirmed at quote time.

MPN
5SL6532-6