Siemens 5SU1354-0LB13 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SU1354-0LB13 SENTRON RCBO, 13 A, B Curve, 10 kA

MPN5SU1354-0LB13

Siemens SENTRON 5SU1 RCBO, 1P+N, 13 A rated current, B tripping characteristic, 10 kA breaking capacity per EN 60898, AC fault current type, 2 MW, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SU1354-0LB13 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU1354-0LB13 — Identification
ParameterValue
Product designationRCBO
5SU1354-0LB13 — Mechanical
ParameterValue
Mounting positionany
Maximum4.8 W
Width36 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU1354-0LB13 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU1354-0LB13 — Electrical
ParameterValue
Tripping Characteristic ClassB

Product details

The Siemens 5SU1354-0LB13 is a SENTRON RCBO — a combined residual-current and overcurrent protective device — in a 1P+N configuration, meaning it switches the line conductor and monitors the neutral for ground faults while providing overcurrent protection on the line side only.

Above that, the device derates: 12.48 A at 40 °C, 12.22 A at 45 °C, 11.96 A at 50 °C, 11.57 A at 55 °C, 11.31 A at 60 °C, 10.53 A at 65 °C, and 10.01 A at 70 °C. The fault-current type is AC-only (senses sinusoidal residual currents). For pulsating DC or smooth DC fault currents, a type A or type B RCBO would be needed. Energy limiting class 3 indicates it lets through less let-through energy (I²t) than class 1 or 2 devices, reducing stress on downstream cables and components during a fault.

It accepts solid or stranded conductors from 0.75 mm² up to 35 mm² — covering everything from 1.5 mm² lighting circuits to 10 mm² feeder tails. The supply can enter from either top or bottom, which simplifies busbar routing in a crowded distribution board. IP20 with the distribution board installed and conductors connected; the front face is finger-safe only when the board cover is closed. Mounting position is any — the device operates correctly upright, sideways, or inverted, which helps when the DIN rail is oriented vertically.

The RCBO is designed to EN 60898 (the European standard for circuit-breakers for overcurrent protection in household and similar installations) and carries the CE marking. The device is classified per DIN EN 61346-2 and DIN EN 81346-2 as function code F (protective device). The minimum test voltage for the integral test circuit is 195 V AC — the test button will not operate correctly below that line voltage.

Frequently asked questions

Where can I buy the 5SU1354-0LB13 and what is the lead time?

The part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quotation — no stock or lead-time figure is published here.

What is the closest functional alternative — can the 5SU9354-7KK16 replace it?

The 5SU9354-7KK16 is a functionally similar SENTRON RCBO with the same 1P+N, B curve, and 10 kA breaking capacity, but it is rated 16 A (not 13 A) and detects type A residual currents (pulsating DC) rather than type AC (sinusoidal only). Verify the load current and the fault-current type before substituting.

What is the depth of the 5SU1354-0LB13?

The overall depth is 77 mm, with an installation depth of 70 mm behind the panel cover.

What conductor sizes does the 5SU1354-0LB13 accept?

It accepts solid or stranded conductors from 0.75 mm² up to 35 mm².

Will the 5SU1354-0LB13 drop into a panel wired for the 5SU9354-7KK16?

The physical footprint is identical — both are 2 MW (36 mm wide) DIN-rail devices with the same depth and connection range. The wiring terminals accept the same conductor sizes. The substitution depends on whether the 13 A rating and AC-only residual detection match the circuit requirements, not on panel fit.

What compliance documentation does Siemens provide for the 5SU1354-0LB13?

The device is designed to EN 60898 and carries CE marking. It is halogen-free and silicon-free. The manufacturer provides a declaration of conformity and technical data sheet; RoHS and REACH compliance information is available from Siemens upon request.