Skip to main content
Siemens 5SU9326-1CN10 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SU9326-1CN10 RCBO, 10A, 30mA, Type C, 6kA

MPN5SU9326-1CN10

Siemens SENTRON 5SU9326-1CN10, RCBO, 2-pole, 10 A rated, 30 mA residual current, Type C trip curve, 6 kA breaking capacity per EN 60898.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SU9326-1CN10 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SU9326-1CN10 — Identification
ParameterValue
Product designationRCD-operated circuit breaker
Product design / constructionInstantaneous
5SU9326-1CN10 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum75 °C
Minimum-40 °C
Width72 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SU9326-1CN10 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors
5SU9326-1CN10 — Electrical
ParameterValue
Tripping Characteristic ClassC

Product details

It protects a 230/240 V AC circuit against both overload/short-circuit (via the Type C magnetic trip) and earth leakage (30 mA residual current).

Rated 10 A at 30 °C ambient, but the thermal derating is significant: 8.9 A at 40 °C, 8.6 A at 45 °C, 8.1 A at 50 °C, and 7.7 A at 55 °C. The Type C characteristic (5–10x In magnetic release) suits motor, lighting, and transformer inrush without nuisance tripping. The 30 mA residual sensitivity covers personnel protection (indirect contact) and fire prevention; it's the standard threshold for socket-outlet circuits in most IEC-based codes.

Snaps onto DIN rail in any mounting position. 4 module-widths wide (72 mm), 77 mm deep, 90 mm tall, with an installation depth of 70 mm. Halogen-free and silicon-free construction, which matters for environments with sensitive electronics or strict fire-safety requirements (e.g., rail, marine, or data-center auxiliary boards).

Frequently asked questions

What is the breaking capacity of 5SU9326-1CN10?

6 kA per EN 60898 and also 6 kA per IEC 60947-2. That covers standard domestic and light commercial distribution boards; for higher fault-current panels, check the upstream SCCR coordination.

Does the 5SU9326-1CN10 drop into a panel designed for the 5SL4363-7?

No direct footprint match is claimed. The 5SU9326-1CN10 is a 4-module-wide RCBO; the 5SL series are standard MCBs. Verify the DIN-rail space and wiring diagram — the RCBO occupies more width and has the additional residual-current connections.

Where can I buy 5SU9326-1CN10 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price.

MPN
5SU9326-1CN10