Skip to main content
Siemens 5SV5614-6 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SV5614-6 SENTRON RCCB, 40A 300mA Type A, 2-Pole

MPN5SV5614-6
Active

Siemens SENTRON RCCB, 2-pole Type A, In: 40A, 300mA, Un AC: 230V, instantaneous, DIN rail mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SV5614-6 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SV5614-6 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SV5614-6 — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-5 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SV5614-6 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SV5614-6 is a SENTRON residual current operated circuit breaker (RCCB), 2-pole, Type A, rated 40 A with a 300 mA trip threshold, designed for 230 V AC residential and commercial distribution boards.

The 5SV5614-6 is an instantaneous (non-delayed) Type A RCCB, meaning it trips immediately on detecting a sinusoidal AC residual current or a pulsed DC residual current up to 300 mA. Type A covers the typical waveforms from single-phase rectified loads — switch-mode power supplies, LED drivers, computer equipment — which a plain Type AC RCCB would not detect. The 6 kA short-circuit current rating (SCCR) per IEC 61008-1 is the withstand rating for the device itself under fault; the conditional rated short-circuit current with a backup MCB is 0.5 kA per EN 60898, which is the coordination value you size the upstream MCB to.

Mounts on a DIN rail (REG) in any position. The 70 mm installation depth is shallower than some legacy RCCBs, which helps in compact enclosures where cable bending radius is tight.

The silicon-free construction is relevant for applications where silicone outgassing could contaminate contacts or optical surfaces. The mechanical service life is 3,000 switching cycles typical.

Frequently asked questions

What is the 5SV5614-6 used for?

It is a 2-pole Type A residual current circuit breaker (RCCB) rated 40 A with a 300 mA trip threshold for 230 V AC circuits. It provides earth leakage protection in residential and commercial distribution boards, particularly where switch-mode power supplies or rectified loads are present.

Will the 5SV5614-6 fit in a panel designed for a 5SY5240-7?

Both are 2-MW wide (36 mm) DIN-rail devices with 70 mm installation depth, so the 5SV5614-6 will physically drop into the same panel footprint. However, the 5SY5240-7 is a miniature circuit breaker (MCB) with a different function and trip characteristic; the 5SV5614-6 is an RCCB and cannot be used as a direct functional replacement for an MCB without rewiring the circuit.

MPN
5SV5614-6