Combined terminal top and bottom accepts conductors for loop-through wiring.
Rated current is 10 A at 35 °C; derate to 9.52 A at 40 °C, 9.27 A at 45 °C, 9.02 A at 50 °C, 8.75 A at 55 °C, and 8.48 A at 60 °C — the derating curve matters when the breaker is packed tightly in a warm cabinet. Maximum relative humidity is 95% up to 55 °C, decreasing to 55% at 70 °C and 35% at 75 °C — a consideration for railway or industrial environments with condensation risk.