Siemens 5SY7110-8CC — 1-Pole MCB (DIN Rail)

Siemens 5SY7110-8CC SENTRON MCB, D Curve, 1-Pole, 15 kA

MPN5SY7110-8CC

Siemens SENTRON 5SY7110-8CC, 1-pole miniature circuit breaker, D tripping characteristic, 15 kA (EN 60898), 25 kA (IEC 60947-2), 400 V AC, 1 MWU, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7110-8CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Pole design1P
Application suitabilityMechanical engineering / industry
5SY7110-8CC — Electrical & Protection
ParameterValue
Tripping characteristic classD
Overvoltage categoryIII
5SY7110-8CC — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7110-8CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

What it is and what it does

The Siemens 5SY7110-8CC is a 1-pole SENTRON miniature circuit breaker with a D tripping characteristic, designed to protect branch circuits against overloads and short circuits in industrial control panels and mechanical engineering applications. The D curve means it tolerates high inrush currents — typical for motor loads, transformers, and welding equipment — without nuisance tripping, while still clearing faults at its rated breaking capacity. Rated 15 kA per EN 60898 and 25 kA per IEC 60947-2 at 400 V AC, it handles substantial fault currents in 50/60 Hz systems. Under UL 1077 / CSA C22.2 No.235, the rating is 5 kA — check which standard governs your installation.

Mounting and integration

Snaps onto DIN rail via the quick assembly system, occupying 1 modular width unit (18 mm wide). Mounting position is unrestricted, and the installation depth is 70 mm with a total depth of 76 mm — fits standard enclosures without extra clearance. Combined terminals at top and bottom accept supply from any direction. The breaker is sealable and halogen-free / silicon-free, suitable for sensitive environments like food processing or semiconductor fabs. IP20 protection (with connected conductors) and pollution degree 3 mean it's intended for dry indoor panels — not for washdown or outdoor exposure without an enclosure.

Lifecycle and sourcing

Supplementary devices (auxiliary contacts, shunt trips, alarm switches) can be installed on the right side per the manufacturer's accessory range.

Frequently asked questions

What is 5SY7110-8CC's listed depth (76 mm) on this component line?

The total depth is 76 mm; the installation depth (behind the panel face) is 70 mm.

What is 5SY7110-8CC's listed width (18 mm) on this component line?

Width is 18 mm, which is 1 modular width unit (MWU) on standard DIN rail.

MPN
5SY7110-8CC