Skip to main content
Siemens 5SY7213-6 — 2-Pole MCB (DIN Rail)

Siemens 5SY7213-6 SENTRON MCB, 2P B-Curve, 15/25 kA

MPN5SY7213-6
Active

Siemens SENTRON miniature circuit breaker, 5SY7213-6, 2-pole, B characteristic, 15 kA (EN 60898) / 25 kA (IEC 60947-2), 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7213-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentMechanical engineering / industry
5SY7213-6 — Electrical
ParameterValue
Number of poles2
5SY7213-6 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SY7213-6 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SY7213-6 — Environmental
ParameterValue
Pollution degree3
5SY7213-6 — Specifications
ParameterValue
At AC rated value400 V
According to EN 60898 rated value15 kA
With single-phase operation at AC rated value440 V
Energy Limitation Class3

Product details

Siemens 5SY7213-6 SENTRON MCB — 2-pole B-curve for industrial panel protection

Breaking capacity is 15 kA per EN 60898-1 and 25 kA per IEC 60947-2, with a 5 kA rating under UL 1077 / CSA C22.2 No. 235 for North American panels.

Breaking capacity and standard compliance

This breaker is certified to both IEC/EN 60898-1 and IEC/EN 60947-2, plus UL 1077. The 15 kA rating under 60898-1 covers the residential and light commercial duty cycle; the 25 kA rating under 60947-2 is the figure that matters for industrial coordination studies where higher fault current is expected. At DC (60–72 V) it interrupts 15 kA per IEC 60947-2. The 5 kA UL 1077 rating means it qualifies as a supplementary protector in North American control panels — not a branch-circuit rated device under UL 489, so verify your local code before specifying it as the sole overcurrent device on a feeder.

Environmental and installation notes

Rated for ambient temperatures from -40 °C to 75 °C, with humidity derating above 55 °C (max 95% RH at 55 °C, tapering to 35% at 75 °C).

Frequently asked questions

What is the breaking capacity of 5SY7213-6?

15 kA per EN 60898-1, 25 kA per IEC 60947-2 at 400 V AC, and 15 kA at 60–72 V DC per IEC 60947-2. Under UL 1077 it is rated 5 kA.

Where can I buy 5SY7213-6?

The part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

What compliance documentation does the 5SY7213-6 carry?

It is certified to IEC/EN 60898-1, IEC/EN 60947-2, and UL 1077 / CSA C22.2 No. 235. The housing is halogen-free and silicon-free.

Will 5SY7213-6 drop into a panel specified for 5SY7210-7CC?

Both are 2-pole SENTRON MCBs on a 36 mm footprint with the same DIN-rail mounting, so the mechanical fit is identical. The difference is the tripping characteristic: 5SY7213-6 is B-curve (3–5× In), while 5SY7210-7CC carries a different characteristic. Verify the required curve for your circuit before substituting.

MPN
5SY7213-6