Siemens 5SY7213-7 — 13 A C-Curve 2-Pole MCB
Breaking capacity is 15 kA per EN 60898 and 25 kA per IEC 60947-2 at 230/400 V AC; DC breaking capacity per IEC 60947-2 is 15 kA. That 25 kA figure under 60947-2 gives headroom for industrial panels where fault currents run higher than the residential EN standard covers — useful when specifying for a machine feeder rather than a lighting sub-board. Temperature derating is published: at 40 °C the continuous rating drops to 12.38 A, at 50 °C to 11.73 A, and at 60 °C to 11.02 A.
Fit and mounting
Depth is 76 mm, installation depth 70 mm; overall dimensions 90 x 36 x 76 mm (H x W x D). Pollution degree 3, overvoltage category III — rated for the typical industrial control panel environment. Sealable, halogen-free, silicon-free construction. IP20 with connected conductors — standard for a DIN-rail enclosure; no washdown rating, so keep it inside the cabinet.
Lifecycle status is current — no end-of-life notice, no last-time-buy window.