The 400 V AC rating and 15 kA breaking capacity per EN 60898 (20 kA per IEC 60947-2) tell you it can interrupt a fault up to those levels without upstream damage, which matters for selectivity coordination in a distribution panel. The current derates with ambient temperature: 37.6 A at 45 °C, 36.76 A at 50 °C, 35.92 A at 55 °C, 35.04 A at 60 °C.
Installation depth is 70 mm. Mounting position is any, so vertical or horizontal orientation works in tight enclosures. Sealable design allows padlocking the toggle in the off position for lockout/tagout.