Skip to main content
Siemens 5SY8510-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY8510-7 SENTRON MCB, C-Curve 2-Pole 40 kA

MPN5SY8510-7
Active

Siemens SENTRON 5SY8510-7 miniature circuit breaker, C-curve, 2-pole (1P+N), 40 kA at 230 V AC per IEC 60947-2, 36 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY8510-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityMechanical engineering / industry
5SY8510-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SY8510-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY8510-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SY8510-7 SENTRON MCB — C-Curve, 40 kA, 2-Pole

It carries a 40 kA rated short-circuit breaking capacity at 230 V AC per IEC 60947-2, and 15 kA at 60 V DC per the same standard. For UL 1077 applications, the interrupting rating is 5 kA. This is a current-production part, actively sourced through independent distribution.

The 15 kA DC rating at 60 V applies to DC control circuits or battery-backed loads — verify the DC voltage does not exceed 72 V. The 5 kA UL 1077 rating is the supplementary-protector limit for North American panels where the breaker is not the sole branch-circuit overcurrent device.

The 5SY8510-7 occupies 2 modular width units (36 mm) on a DIN rail, with a depth of 76 mm and an installation depth of 70 mm. It mounts in any position and uses a quick-assembly fastening system. IP20 protection applies with connected conductors; the enclosure is sealable for tamper-proofing in accessible locations.

Frequently asked questions

What is the breaking capacity of 5SY8510-7?

40 kA at 230 V AC per IEC 60947-2, 15 kA at 60 V DC per IEC 60947-2, and 5 kA per UL 1077.

What is the width and depth of 5SY8510-7?

Width is 36 mm (2 modular units), depth is 76 mm, installation depth is 70 mm.

Where can I buy 5SY8510-7 and get current pricing?

The 5SY8510-7 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Does 5SY8510-7 switch the neutral?

Yes, the neutral conductor is switched, making it a 1P+N design despite the 2-pole form factor.

What standards does 5SY8510-7 comply with?

It complies with IEC/EN 60947-2 and UL 1077. It is also halogen-free and silicon-free.

MPN
5SY8510-7