Skip to main content
Siemens 6AG1321-7RD00-4AB0 — PLC I/O & Expansion Modules

Siemens 6AG1321-7RD00-4AB0 SIPLUS SM 1321, 4xNAMUR, -40..70°

MPN6AG1321-7RD00-4AB0

Siemens SIPLUS SM 1321, digital input module, 4 NAMUR inputs, -40..70 °C, ATEX II 3 G Ex nA [ib Gb], UL File E239877.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

6AG1321-7RD00-4AB0 — I/O
ParameterValue
Digital inputs4
6AG1321-7RD00-4AB0 — Electrical
ParameterValue
Rated value (DC)8.2 V; from internal power circuit supply
Max.70 °C
Power loss (typ.)1.1 W
Current consumption from backplane bus (5 V DC), max.80 mA
Current consumption from load voltage L+ (no load), max.50 mA
Reverse polarity protectionYes
Isolation: between channelsYes; 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
Isolation: channels to backplane busYes; 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
Max. cable length, unshielded200 m
6AG1321-7RD00-4AB0 — Performance
ParameterValue
ParameterizableYes; 0.1 / 0.5 / 3 / 15 / 20 ms (plus 0.25 ms preparation time)
Diagnostics functionYes
Group fault indicator (SF, red LED)Yes
6AG1321-7RD00-4AB0 — Environmental
ParameterValue
Min.-40 °C
6AG1321-7RD00-4AB0 — Mechanical
ParameterValue
Height125 mm
Width40 mm
Depth120 mm
Weight (approx.)230 g
6AG1321-7RD00-4AB0 — Approvals
ParameterValue
CE markYes

Product details

The 6AG1321-7RD00-4AB0: The NAMUR interface supplies 8.2 V from the internal power circuit to each channel, with a no-load voltage of 10 V max and short-circuit current limited to 14.1 mA. Power output per channel is capped at 33.7 mW, keeping the loop intrinsically safe. Reverse polarity protection is built in. Channel-to-channel isolation is 60 V DC / 30 V AC in the hazardous area and 400 V DC / 250 V AC outside it — allowing mixed wiring with non-Ex circuits in the same panel.

The module occupies a 40 mm wide slot on the DIN rail, 125 mm tall and 120 mm deep. It connects to the backplane via the 20-pin front connector and draws up to 80 mA from the 5 V DC bus. Typical power loss is 1.1 W. Diagnostics are readable over the backplane; a red SF group error LED and per-channel red fault indicator flash on short-circuit or wire-break. Green status LEDs confirm channel state.

Frequently asked questions

What are the operating temperature limits?

Rated for ambient temperature from -40 °C to 70 °C.

What approvals does this module carry?

UL (File E239877), ATEX II 3 G for hazardous areas, CE, KC, EAC, and RCM (C-TICK).

MPN
6AG1321-7RD00-4AB0