Skip to main content
Siemens 6AG1321-7RD00-4AB0

Siemens 6AG1321-7RD00-4AB0 SIPLUS SM 1321, 4xNAMUR, -40..70°

MPN 6AG1321-7RD00-4AB0

Siemens SIPLUS SM 1321, digital input module, 4 NAMUR inputs, -40..70 °C, ATEX II 3 G Ex nA [ib Gb], UL File E239877.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

6AG1321-7RD00-4AB0 specifications
ParameterValue
Temp operating max10 °C
Temp operating min-20 °C
Depth120 mm
Width40 mm
Height125 mm

Product details

The 6AG1321-7RD00-4AB0: The NAMUR interface supplies 8.2 V from the internal power circuit to each channel, with a no-load voltage of 10 V max and short-circuit current limited to 14.1 mA. Power output per channel is capped at 33.7 mW, keeping the loop intrinsically safe. Reverse polarity protection is built in. Channel-to-channel isolation is 60 V DC / 30 V AC in the hazardous area and 400 V DC / 250 V AC outside it — allowing mixed wiring with non-Ex circuits in the same panel.

The module occupies a 40 mm wide slot on the DIN rail, 125 mm tall and 120 mm deep. It connects to the backplane via the 20-pin front connector and draws up to 80 mA from the 5 V DC bus. Typical power loss is 1.1 W. Diagnostics are readable over the backplane; a red SF group error LED and per-channel red fault indicator flash on short-circuit or wire-break. Green status LEDs confirm channel state.

MPN
6AG1321-7RD00-4AB0