The 6SL32.0-.YE26-.A.0 is a SINAMICS G120X infrastructure converter, part of the family built for HVAC, water, and wastewater applications. Rated power is 11 kW at 110% overload for 60 s and 100% for 240 s, on a 380-480 VAC three-phase supply at 47-63 Hz. That duty cycle covers pump and fan loads where short-term overload is the norm, not continuous high-torque. The integrated radio interference suppression filter meets category C2, so it can be installed in first-environment (residential) zones without external filtering.
Size FSC with IP20 / UL open type protection — panel-mount only, no washdown rating. Ambient temperature range -20 to +45 °C covers most mechanical rooms. The C2 filter is built in, so no add-on box; the drive lands on the backplate with the standard Siemens footprint for this frame size.