30 kW rating and overload capability for motor sizing
The 6SL3210-1KE26-0AF1: Rated power 30.0 kW with 150% overload for 3 seconds — this overload envelope matches constant-torque loads like conveyors and extruders where the motor draws peak torque during breakaway. For variable-torque loads (pumps, fans), the drive can run continuously at the 30 kW rating without the overload headroom being consumed. Input voltage range 3AC 380-480 V +10/-20% at 47-63 Hz covers both 400 V and 480 V global line voltages without an external transformer. The wide frequency tolerance accommodates generator supply or weak grid conditions common on construction sites and remote installations.
I/O complement and safety integration for standalone control
Onboard I/O: 6 digital inputs, 2 digital outputs, 1 analog input, 1 analog output — sufficient for a standalone pump or compressor station without an expansion module. The analog input accepts 0-10 V or 4-20 mA for setpoint from a pressure transducer or PLC analog card. Safe Torque Off (STO) integrated per SIL 3 / PL e eliminates the need for an external safety relay in most guarding applications. The STO function removes motor torque without disconnecting the mains power, enabling safe access to the driven machine during setup or maintenance. PROFINET-PN fieldbus interface — native real-time Ethernet for direct connection to Siemens S7-1200/1500 controllers without a gateway. The drive exchanges process data and parameter access over the same cable, reducing wiring and cabinet space.
Panel integration and environmental constraints
IP20 / UL Open Type enclosure — panel-mount only; the drive requires an IP54 or higher cabinet for washdown or outdoor duty. The Size FSD footprint (472 x 200 x 237 mm HxWxD) needs a minimum 500 mm panel depth to allow cable bending radius below the power terminals. External 24 V supply required for control logic — the drive does not derive the control voltage from the DC bus. A separate 24 VDC power supply (typically 2-3 A) must be provisioned in the panel for the control board, I/O, and fieldbus interface. Integrated Class A EMC filter meets EN 61800-3 for industrial environments. For residential or sensitive-grid installations (first environment, restricted distribution), an external Class B filter may be required between the drive and the mains.
Compliance documentation for tender and audit
RoHS compliant since 2017-02-13. REACH Article 33 disclosure: lead (CAS 7439-92-1) present above 0.1% w/w in certain components — this must be declared in EU tender submissions per REACH requirements. Export Control Classification: AL N / ECCN 9N9999 — no strategic trade restrictions. Standard customs clearance applies for international shipments.