Drive rating and overload profile
The 6SL3210-1KE32-1UF1: Rated power 110.0 kW with 150% overload for 3 seconds — this is the short-term peak torque capability for breakaway or jam clearing, not the continuous rating. The 3-second window means the drive can deliver 1.5× rated current momentarily, but the I²t thermal model in the control board will fold back if the overload persists beyond that. Input supply is 3-phase 380-480 V +10/-20%, 47-63 Hz, unfiltered. The unfiltered input means the drive does not include an internal EMC filter; for CE-marked installations you will need an external line filter to meet conducted emission limits.
I/O and fieldbus interface
The I/O interface provides 6 digital inputs, 2 digital outputs, 1 analog input, and 1 analog output — enough for basic speed control, enable, and fault feedback without an expansion module. The integrated PROFINET-PN fieldbus allows direct connection to a Siemens S7-1500 or other PN controller; the drive appears as a PROFIdrive device on the network. Safe Torque Off (STO) is integrated, meeting SIL 3 / PL e for safety-related shutdown without an external safety relay. The STO function disables the power stage independently of the control logic.
Mechanical and compliance
Size FSF enclosure — 708 x 305 x 357 mm (H x W x D) — with IP20 / UL Open Type protection. The IP20 rating means it is protected against solid objects >12 mm but not against moisture; install in a dry, clean cabinet. The packaging dimensions are 745 x 469 x 385 mm, so plan for a carton that fits standard pallet footprints. RoHS compliant since 13-02-17, with REACH Article 33 notification for lead (CAS 7439-92-1) above 0.1% w/w. The export control classification is AL: N / ECCN: 9N9999 — no special license required for most destinations.