Active production — still a current BOM line
The 6SL3210-1PE28-8UL0: For the MRO planner, that means it stays a valid spare for the SINAMICS G120 fleet without needing a cross-reference or board spin.
Duty ratings that decide the drive fit
High overload rating is 37 kW with 200% current for 3 seconds, 150% for 57 seconds, 100% for 240 seconds — this handles heavy starting loads like crushers or extruders where the motor draws double rated current briefly. Low overload rating is 45 kW with 150% for 3 seconds, 110% for 57 seconds — suited for variable-torque loads like centrifugal pumps and fans. Input is 3-phase 380–480 VAC +10/-20%, 47–63 Hz. The built-in braking chopper means you don't need an external braking unit for deceleration duty — just add a resistor sized for the stopping energy.
Ambient limits and mounting constraints
Rated for -20 to +50 °C ambient in high-overload mode; low-overload mode derates to +40 °C. IP20 enclosure — no washdown protection, but fine for a ventilated cabinet. Dimensions are 551 x 275 x 237 mm (HxWxD), blocksize format with FSE protection. The module ships without a Control Unit or operator panel — you supply the CU (e.g., CU240E-2 or CU250S-2) and mate it via the internal interface. Approved for CU firmware version V4.7 HF8; confirm the CU firmware matches before commissioning.
Compliance and documentation
RoHS compliant since January 2017. REACH Article 33 declares lead (CAS 7439-92-1) above 0.1% w/w in certain components — relevant for end-of-life reporting in EU markets. Export control is AL (N) / ECCN 9N9999 — no special license required for most industrial destinations. The product group code is 9775; group code R220.