Duty ratings that govern the real application
The 6SL3210-1PE32-1UL0: The module delivers 90 kW in high-overload duty (HO) with a 200% overload for 3 seconds, 150% for 57 seconds, and 100% for 240 seconds, at an ambient range of -20 to +50 °C. In low-overload duty (LO) it delivers 110 kW with 150% for 3 seconds, 110% for 57 seconds, and 100% for 240 seconds, at -20 to +40 °C ambient. The 3AC 380-480 V +10/-20% input range at 47-63 Hz covers standard global industrial mains without a step-down transformer. The built-in braking chopper handles regenerative energy from fast deceleration — no external braking module needed for most applications. The blocksize format (708 x 305 x 357 mm HxWxD) is designed for panel mounting with air cooling clearance around the heatsink.
Compliance and documentation for the quality file
RoHS compliant since January 1, 2017. Under REACH Article 33, the module contains lead (CAS 7439-92-1) above 0.1% w/w in certain components — this disclosure is required for downstream users and should be noted in your material compliance register. Export control classification is AL: N / ECCN: 9N9999, meaning no special export license is required for most commercial destinations. The product class is A — a standard stock item eligible for return within the standard returns policy period, assuming original packaging and no damage.