Skip to main content
Siemens 6SL3210-1RE28-8UL0 — AC Drives (VFD)

Siemens 6SL3210-1RE28-8UL0 SINAMICS G120 PM240P-2, 37 kW HO

MPN6SL3210-1RE28-8UL0
NRND

Siemens SINAMICS G120 PM240P-2 Power Module, 6SL3210-1RE28-8UL0, unfiltered, 3-phase 380-480 V AC, 37 kW high overload, 45 kW low overload, IP20, FSE protection.

$2,959.10Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

6SL3210-1RE28-8UL0 — Identification
ParameterValue
Product familyPM240P-2 Power Modules

Other specifications

6SL3210-1RE28-8UL0 — Other specifications
ParameterValue
Group codeR220
Product group5678
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
Export control regulationsAL : N / ECCN : 9N9999
Compliance with the substance restrictions according to RoHS directiveSince: 22-12-16

Product details

Power module for the SINAMICS G120 — PM240P-2 unfiltered

The 6SL3210-1RE28-8UL0 is a SINAMICS G120 PM240P-2 power module, unfiltered, rated for 3-phase 380-480 V AC input at 47-63 Hz. In high-overload (HO) duty it delivers 37 kW with 150 % overload for 60 seconds and 100 % continuous for 240 seconds, at an ambient range of -20 to +50 °C. For low-overload (LO) applications it supports 45 kW with 135 % for 3 seconds and 110 % for 57 seconds, at -20 to +40 °C ambient. This is a Class C product — manufactured to order, not a stocked shelf item. The form factor is 551 x 275 x 237 mm (H x W x D) with IP20 protection and FSE (full-safe enclosure) protection. It ships without a Control Unit or operator panel; the CU firmware version required is V4.7 SP6 HF1 or later.

NRND — what it means for your BOM line

Siemens lists this power module as NRND (Not Recommended for New Designs). That means it is still available for existing installations and MRO spares, but the manufacturer advises against specifying it for new projects. For a line-down replacement or a legacy BOM position, the NRND status is manageable — the part is still manufacturable to order.

Compliance and documentation

RoHS compliant since 22-12-16. REACH Article 33 disclosure applies: lead (CAS 7439-92-1) is present above 0.1 % w/w. Export control classification is AL: N / ECCN: 9N9999.

Frequently asked questions

What is the difference between high overload and low overload on this drive?

High overload (HO) delivers 37 kW with 150 % overload for 60 seconds and 100 % for 240 seconds, at -20 to +50 °C ambient. Low overload (LO) delivers 45 kW with 135 % for 3 seconds and 110 % for 57 seconds, at -20 to +40 °C. LO suits constant-torque applications where the duty cycle stays flat.

What compliance documentation does Siemens provide for 6SL3210-1RE28-8UL0?

RoHS compliance is confirmed since 22-12-16. REACH Article 33 disclosure applies due to lead (CAS 7439-92-1) above 0.1 % w/w. Export control is AL: N / ECCN: 9N9999.

MPN
6SL3210-1RE28-8UL0