355 kW at 135% overload — HVAC and water duty cycle
The 6SL3220-1YE58-1CB0: Rated 355 kW continuous with a 135% overload for 3 s, 110% for 60 s, and 100% for 240 s — this overload profile matches the starting and stall conditions of centrifugal pumps and fans in HVAC and water/wastewater applications where the drive must ride through transient load spikes without tripping. Operates on 3AC 380-480 V +10/-20% at 47-63 Hz, covering the global low-voltage industrial mains range without a transformer tap change.
Fieldbus integration and enclosure class
Built-in MODBUS RTU, BACnet MS/TP, and USS on the same port — no option card needed for BMS or SCADA integration. The IP20 / UL open type enclosure means the drive mounts inside a panel with the gland plate handling cable entry; it is not rated for standalone washdown or outdoor installation. Size FSH frame with packaging dimensions 800 x 1,870 x 600 mm — plan the panel depth and lifting gear before the drive arrives on site. The integrated RFI suppression filter is category C3, suitable for industrial second-environment (non-residential) installations where the drive is hard-wired behind a transformer or dedicated supply.
Compliance and substance declarations
RoHS compliant since 11-03-20. REACH Article 33 declares lead (CAS 7439-92-1) above 0.1% w/w in certain components — this triggers the duty to inform downstream users under EU REACH, so the declaration travels with the drive into the end-product BOM. Export Control Regulations: AL N / ECCN EAR99H — no special license required for most commercial shipments, but confirm the destination country's own controls.