Skip to main content
Siemens 6SL3220-1YE66-0CF0 — AC Drives (VFD)

Siemens 6SL3220-1YE66-0CF0 SINAMICS G120X VFD, 560 kW

MPN6SL3220-1YE66-0CF0
Active

Siemens SINAMICS G120X infrastructure converter, 6SL3220-1YE66-0CF0, 560 kW, 380-480 V 3AC, IP20, frame size FSJ, with integrated C3 EMC filter and PROFINET PN/Ethernet IP fieldbus.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

6SL3220-1YE66-0CF0 — Identification
ParameterValue
Product familySINAMICS G120X infrastructure converters for HVAC/Water/Wastewater

Other specifications

6SL3220-1YE66-0CF0 — Other specifications
ParameterValue
Group codeR220
Product group4R53
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
Export control regulationsAL : N / ECCN : 3A999A
Compliance with the substance restrictions according to RoHS directiveSince: 11-03-20

Product details

560 kW drive for HVAC and water infrastructure

The 6SL3220-1YE66-0CF0 is a SINAMICS G120X infrastructure converter rated at 560 kW with a 135% overload for 3 seconds or 110% for 60 seconds, and 100% for 240 seconds — the overload profile matches variable-torque loads like fans, pumps, and compressors in HVAC and water/wastewater applications. It operates from a 380-480 V 3AC supply (+10/-20%) at 47-63 Hz and includes a radio interference suppression filter for category C3, which means it's suited for industrial environments where the drive is installed in a separate enclosure from the mains supply — not for residential or first-environment installations without additional filtering.

Fieldbus and control integration

No operator panel or IO expansion is included as standard; commissioning is done through the web server, SINAMICS Startdrive, or a connected HMI over the fieldbus link.

Lifecycle and compliance

RoHS compliant since March 2020, with a REACH Article 33 disclosure for lead (CAS 7439-92-1) above 0.1% w/w in certain components — this matters for EU end-of-life reporting and substance declarations. Export control classification is AL: N / ECCN: 3A999A, which covers drives with power handling above a threshold — confirm destination-country licensing requirements before cross-border shipment.

Physical integration and environment

Ambient temperature rating is 0 to +45 °C without derating; above that, output current must be reduced per the SINAMICS G120X derating curves in the operating instructions.