Skip to main content
Siemens 6SL3220-1YH58-1CB0 — AC Drives (VFD)

Siemens 6SL3220-1YH58-1CB0 SINAMICS G120X VFD, 355 kW

MPN6SL3220-1YH58-1CB0
Active

Siemens SINAMICS G120X infrastructure converter, 6SL3220-1YH58-1CB0, 355 kW, 3AC 500-690 V, IP20, Size FSH, with integrated MODBUS RTU, BACnet MS/TP, USS.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

6SL3220-1YH58-1CB0 — Identification
ParameterValue
Product familySINAMICS G120X infrastructure converters for HVAC/Water/Wastewater

Other specifications

6SL3220-1YH58-1CB0 — Other specifications
ParameterValue
Group codeR220
Product group4R53
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
Export control regulationsAL : N / ECCN : EAR99H
Compliance with the substance restrictions according to RoHS directiveSince: 11-03-20

Product details

355 kW at 500-690 V — overload profile for pump and fan loads

The 6SL3220-1YH58-1CB0: This SINAMICS G120X drive delivers 355 kW rated power with an overload capability of 135 % for 3 s, 110 % for 60 s, and 100 % for 240 s — a profile matched to centrifugal pump and fan starting duty where peak torque is brief and the running load is steady. The 3AC 500-690 V +10/-20 % input range covers European 690 V industrial mains and 575 V North American grids without a step-down transformer, though the RFI filter is category C3, intended for industrial environments with a dedicated transformer secondary.

Integrated fieldbus and enclosure constraints

MODBUS RTU, BACnet MS/TP, and USS are on-board — no option module needed for BMS integration in HVAC or water/wastewater plants. The drive ships without an operator panel; a separate panel or PC connection is required for commissioning. The packaging dimensions (800 x 1870 x 600 mm) give a sense of the crate size for logistics planning.

Active production, made-to-order lead time

RoHS compliant since March 2020. REACH Article 33 declares lead (CAS 7439-92-1) above 0.1 % w/w in certain components — the supplier provides the full declaration on request. Export control is AL:N / ECCN EAR99H, so no special licensing for most commercial destinations.

MPN
6SL3220-1YH58-1CB0