400 kW at 500-690 V — the load rating that governs the BOM line
The 6SL3220-1YH60-0CF0: Rated 400 kW for 135% overload for 3 seconds or 110% for 60 seconds, with 100% continuous at 240 seconds — this is the duty cycle that decides whether the drive holds a pump or fan through transient load spikes without tripping. Input range is 3AC 500-690 V +10/-20% at 47-63 Hz, covering the common 575 V and 690 V industrial grids in North America and Europe without a step-down transformer. The integrated EMC filter meets category C3, which means it is suitable for industrial second-environment installations where the supply is from a dedicated transformer — no external filter needed for most plant-floor runs.
Fieldbus and enclosure — what ships on the frame
PROFINET-PN and Ethernet IP are onboard; no option module required for these two protocols. The drive ships without an operator panel or I/O expansion — those are separate order codes if the application needs local HMI or additional I/O. Ambient temperature range is 0 to +45 °C; above that, output current derating applies per the SINAMICS G120X manual.
Lifecycle and compliance — active, RoHS, REACH declared
The product class is C (manufactured/produced to order), which means it is built per order and not stocked as a standard off-the-shelf item. RoHS compliant since 11 March 2020. REACH Article 33 declaration notes lead (CAS 7439-92-1) above 0.1% w/w — this is a standard declaration for industrial power electronics with solder joints and busbars. Export Control Classification: AL: N / ECCN: 3A999A — no special license required for most destinations, but verify against the end-user and end-use before cross-border shipment.