Skip to main content
Siemens 6SL3220-1YH62-1CB0 — AC Drives (VFD)

Siemens 6SL3220-1YH62-1CB0 SINAMICS G120X VFD, 450 kW

MPN6SL3220-1YH62-1CB0
Active

Siemens SINAMICS G120X infrastructure converter, 6SL3220-1YH62-1CB0, 450 kW, 500-690 V 3-phase, IP20, size FSH, with integrated RFI C3 filter and MODBUS RTU/BACnet MS/TP/USS.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

6SL3220-1YH62-1CB0 — Identification
ParameterValue
Product familySINAMICS G120X infrastructure converters for HVAC/Water/Wastewater

Other specifications

6SL3220-1YH62-1CB0 — Other specifications
ParameterValue
Group codeR220
Product group4R53
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
Export control regulationsAL : N / ECCN : EAR99H
Compliance with the substance restrictions according to RoHS directiveSince: 11-03-20

Product details

450 kW overload profile — built for pump and fan duty

The 6SL3220-1YH62-1CB0: Rated power 450 kW with a 135% overload capability for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — this duty cycle matches the starting and transient demands of centrifugal pumps, fans, and compressors in HVAC or water/wastewater service. The drive accepts a 3-phase supply of 500–690 V AC +10%/-20% at 47–63 Hz, covering the common industrial voltage bands in Europe, Asia, and North America without a step-down transformer.

Integrated fieldbus and RFI filter — no option cards needed

Built-in MODBUS RTU, BACnet MS/TP, and USS protocols mean the drive communicates directly with building management systems (BMS) or plant SCADA without a separate communication module — saves a slot and reduces wiring. The integrated RFI suppression filter meets category C3 for 3AC 500–690 V supplies, so the drive is suited for industrial environments where conducted emissions limits apply; no external filter needed for most installations.

Size FSH frame — cabinet planning and ambient limits

Physical dimensions are 800 x 1870 x 600 mm (L x W x H) — this is a floor-standing cabinet-mount drive; plan for a dedicated enclosure or a large panel bay with adequate ventilation clearance around the heatsink. Rated ambient temperature 0 to +45 °C with IP20 / UL open type protection — requires installation inside a cabinet that keeps dust and moisture out; no washdown or outdoor rating.

Active production — compliance and sourcing

RoHS compliant since 11-03-20; REACH Article 33 declares lead (CAS 7439-92-1) above 0.1% w/w — factor this into end-of-life waste reporting for the installation site. Export classification AL: N / ECCN: EAR99H — no special export license required for most destinations, simplifying cross-border procurement for global projects.

Frequently asked questions

What fieldbus protocols does 6SL3220-1YH62-1CB0 support?

MODBUS RTU, BACnet MS/TP, and USS are integrated — no option card needed for BMS or SCADA connectivity.

What is the overload rating of 6SL3220-1YH62-1CB0?

135% for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — suitable for pump and fan starting transients.

MPN
6SL3220-1YH62-1CB0