450 kW at 135% overload — the pump/fan duty ceiling
The 6SL3220-1YH62-1CP0: Rated 450 kW with a 135% overload capability for 3 seconds and 110% for 60 seconds (100% for 240 s). That overload profile matches the starting torque and transient load of large centrifugal pumps and fans — the drive doesn't trip on the inrush, and the motor sees controlled acceleration. Input voltage range is 3AC 500-690 V +10/-20% at 47-63 Hz, covering 525 V, 600 V, and 690 V industrial grids without a step-down transformer. The built-in RFI suppression filter is category C3, compliant for industrial environments with a separate PE connection.
Size FSH, IP20 — panel fit and fieldbus integration
Size FSH enclosure, IP20 / UL open type — mounts inside a standard IP54 or higher panel. The 800 x 1870 x 600 mm package dimensions (L x W x H) mean a floor-standing cabinet section, not a wall-mount. Plan for bottom cable entry and adequate clearance above for the cooling airflow. PROFIBUS DP is integrated on the control board — no external communication module needed. The drive ships without an operator panel; parameterization is done via the fieldbus or a PC tool. IO expansion is available if the onboard I/O count doesn't cover the application.
Active production — no LTB pressure
Lifecycle status is active (mature). The product class C designation means units are manufactured to order — not stocked as off-the-shelf inventory, so lead time is confirmed at RFQ against the specific BOM quantity. RoHS compliance effective 2020-03-11. REACH Article 33 disclosure: lead (CAS 7439-92-1) above 0.1% w/w in certain components — the declaration is available for downstream user compliance. Export control is AL N / ECCN EAR99H, no special license required for most destinations.