Skip to main content
Siemens 6SL3220-1YH64-0CP0 — AC Drives (VFD)

Siemens 6SL3220-1YH64-0CP0 SINAMICS G120X VFD, 500 kW

MPN6SL3220-1YH64-0CP0
Active

Siemens SINAMICS G120X infrastructure converter, 6SL3220-1YH64-0CP0, 500 kW, 500-690 V, 47-63 Hz, IP20, PROFIBUS DP, size FSJ.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

6SL3220-1YH64-0CP0 — Identification
ParameterValue
Product familySINAMICS G120X infrastructure converters for HVAC/Water/Wastewater

Other specifications

6SL3220-1YH64-0CP0 — Other specifications
ParameterValue
Group codeR220
Product group4R53
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
Export control regulationsAL : N / ECCN : EAR99H
Compliance with the substance restrictions according to RoHS directiveSince: 11-03-20

Product details

500 kW at 500-690 V — overload profile for pump and fan duty

The 6SL3220-1YH64-0CP0 is a SINAMICS G120X infrastructure converter rated 500 kW at 500-690 V, 47-63 Hz, with a 135% overload for 3 seconds or 110% for 60 seconds, and 100% for 240 seconds. This overload profile matches the starting and transient demands of centrifugal pumps, fans, and compressors in HVAC and water/wastewater service — the drive handles the inrush without oversizing the power stage. The RFI suppression filter for category C3 is integrated, so the drive meets conducted emission limits for industrial second-environment installations without an external filter. Input voltage tolerance of +10/-20% covers the sag on weak utility feeds common in retrofit projects.

Size FSJ enclosure and IP20 integration

The FSJ frame size delivers 500 kW in an IP20 / UL open-type enclosure — the drive mounts in a clean indoor switchgear lineup or MCC bucket. Packaging dimensions of 1,200 x 1,857 x 800 mm indicate a substantial footprint; plan for floor-mounting with top cable entry and adequate clearance for the integrated filter and bus reactor cooling. Integrated PROFIBUS DP fieldbus eliminates a separate communication module for plants running a PROFIBUS backbone. No operator panel or IO expansion is included — the drive is commissioned via the fieldbus or a connected PC with STARTER/SINAMICS Startdrive.

Active production and compliance documentation

RoHS compliant since March 2020. REACH Article 33 disclosure notes lead (CAS 7439-92-1) above 0.1% w/w in certain components — this is a standard declaration for drives with lead-bearing solder joints and does not restrict installation under current EU exemptions.

Frequently asked questions

What compliance documentation does Siemens provide for 6SL3220-1YH64-0CP0?

RoHS compliance is confirmed since March 2020. REACH Article 33 disclosure identifies lead (CAS 7439-92-1) above 0.1% w/w. Export control is AL N / ECCN EAR99H, meaning no special licensing is required for most destinations.

What is the overload capability of this drive?

The drive delivers 135% rated current for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds. This is a variable-torque overload profile suited for pump and fan starting — not intended for constant-torque loads like conveyors or extruders without derating.

MPN
6SL3220-1YH64-0CP0