Active production — 500 kW drive for HVAC/water infrastructure
The 6SL3220-1YH64-1CF0: Rated 500 kW at 135% overload for 3 s or 110% for 60 s, 100% for 240 s — the overload profile matches typical pump/fan duty where short-duration torque peaks are the design ceiling, not continuous full load. Input range is 3AC 500-690 V +10/-20%, 47-63 Hz, with an integrated RFI suppression filter for category C3 — sized for 690 V industrial grids and meets conducted emission limits for the second environment (industrial) without an external filter.
Fieldbus and I/O — PROFINET PN, Ethernet IP, IO expansion
Fieldbus is integrated PROFINET PN and Ethernet IP — no option module needed; the drive appears as a standard PROFINET device on the control network and can also serve as an EtherNet/IP adapter for Rockwell environments. Comes with IO expansion but without an operator panel — the BOM line expects remote HMI or commissioning via the fieldbus/web server.
Physical fit and ambient limits — IP20, Size FSJ, 0 to +45 °C
Degree of protection IP20 / UL open type — requires installation in a clean, dry enclosure (typical MCC or drive cabinet); not rated for washdown or outdoor exposure. Ambient temperature range 0 to +45 °C — above this, derating applies; the drive cabinet ventilation must keep inlet air below 45 °C at full rated output. Packaging dimensions 1,200 x 1,857 x 800 mm — this is a large-frame drive (Size FSJ); plan for lifting equipment and floor space during installation.
Compliance and substance declarations — RoHS, REACH, export control
RoHS compliant since 2020-03-11. REACH Article 33 declaration: lead (CAS 7439-92-1) > 0.1% w/w — the drive contains lead in certain components (e.g., solder joints), which must be communicated downstream per REACH obligations. Export Control Regulations: AL N, ECCN EAR99H — no special export license required for most destinations; EAR99H covers industrial drives with no national security controls.