Active production, made-to-order — plan the BOM lead time
The 6SL3220-1YH66-1CF0: It carries product class C, meaning it's manufactured to order and cannot be reused or returned against credit — confirm the BOM quantity before committing, because once ordered it's yours. Export control is AL:N / ECCN:EAR99H, so no special license is needed for most commercial destinations — that's one less delay in the procurement chain.
560 kW at 135% overload — sized for pump and fan duty
Rated power is 560 kW with a 135% overload capability for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — the 135% short-duration peak handles the starting inertia of a large centrifugal pump or fan without oversizing the drive. Input voltage range is 3AC 500-690V +10/-20% at 47-63 Hz, covering the 690V industrial grids common in water/wastewater and heavy HVAC installations. The RFI suppression filter is built in for category C3 environments — no external filter needed for most industrial second-environment installations.
PROFINET PN + Ethernet IP onboard — no extra comm module
Fieldbus is integrated: PROFINET PN and Ethernet IP are both on the drive's standard hardware — no option module to order, no slot to populate, and no additional IP address to manage. The drive ships without an operator panel — commissioning is done through the web server or the TIA Portal / Startdrive engineering tool over the PROFINET link.
Size FSJ frame, IP20 — panel-mount integration notes
The FSJ frame size is the largest in the G120X family — packaging dimensions are 1,200 x 1,857 x 800 mm, so plan the enclosure depth and door swing accordingly.
RoHS and REACH compliance documentation
RoHS compliant since 11 March 2020 — the declaration is on file and matches the date code on the nameplate. REACH Article 33 duty-to-inform applies: lead (CAS 7439-92-1) is present above 0.1% w/w in the product — the candidate-list substance declaration is available with the shipment documentation.