Active production — 400 kW HVAC/water drive with PROFIBUS DP
The 6SL3220-2YE60-0CP0 is a SINAMICS G120X infrastructure converter rated 400 kW at 135% overload for 3 seconds or 110% for 60 seconds, 100% for 240 seconds — the overload profile is sized for pump and fan starting torque without oversizing the drive.
380-480 V input, RFI filter C3, IP20 enclosure
Input range is 3AC 380-480 V +10/-20%, 47-63 Hz. The built-in RFI suppression filter meets category C3 — suitable for industrial environments with a dedicated transformer or TN system; not for residential or public low-voltage mains without additional mitigation. Ambient temperature range is 0 to +45 °C; above that, derating applies per the manual. Size FSH packaging dimensions are 800 x 1870 x 600 mm — plan for lifting equipment and panel door clearance during installation. The product class is C (manufactured/produced to order), so it's not a stocked shelf item; lead time is confirmed at quote.
RoHS and REACH compliance
RoHS compliant since 11-03-20. REACH Article 33 duty to inform applies: the article contains lead (CAS 7439-92-1) above 0.1% w/w, which must be communicated in the supply chain. Export control classification is AL: N / ECCN: EAR99H — no special license required for most destinations, but confirm with your trade compliance team for end-use restrictions.