Rated power and overload profile for pump/fan duty
The 6SL3220-2YE60-1CB0: Rated power is 400 kW with a 135% overload for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — a profile matched to centrifugal loads where starting torque is low but process surges can spike briefly. Input accepts 3AC 380-480 V +10/-20% at 47-63 Hz, covering the common global low-voltage industrial mains without a step-down transformer.
Built-in fieldbus and I/O for building automation
Fieldbus is integrated: MODBUS RTU, BACnet MS/TP, and USS — no external gateway card needed for HVAC or water/wastewater networks. Comes with a Basic Operator Panel and IO expansion, so local commissioning and digital/analog I/O are ready out of the box.
Lifecycle and compliance — active production, RoHS/REACH documented
RoHS compliant since March 2020; REACH Article 33 declares lead (CAS 7439-92-1) above 0.1% w/w in certain components — the declaration is available for downstream compliance reporting.
Enclosure and mounting for panel integration
Size FSH frame; packaging dimensions are 800 x 1870 x 600 mm, so plan for a floor-mount cabinet with adequate lifting provision.