500 kW at the overload profile that matters
The 6SL3220-2YE64-0CP0: This SINAMICS G120X drive is rated for 500 kW continuous with a 135% overload for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — the overload profile matches pump and fan duty cycles where the peak torque is brief and the sustained load stays at nameplate. The input accepts 3AC 380-480 V +10/-20% at 47-63 Hz, covering the global low-voltage mains range without a transformer tap change.
Built for HVAC/water infrastructure panels
Size FSJ enclosure with IP20 / UL open type protection — it mounts in a ventilated cabinet where the ambient stays between 0 and +45 °C; above that, derate the output current per the drive's thermal curve. The built-in RFI suppression filter meets category C3, so it can be installed on a TN or TT system with a short motor cable run without an external filter for conducted emissions compliance. Integrated PROFIBUS DP fieldbus — no separate communication module needed for a Profibus network; the Basic Operator Panel (BOP) is included for local parameter access and commissioning.
Active production, built to order
Product class C means it is manufactured to order and cannot be returned or reused — confirm the BOM line before committing, and note the packaging dimensions: 1,200 x 1,857 x 800 mm. RoHS compliant since March 2020, with a REACH Article 33 disclosure for lead (CAS 7439-92-1) above 0.1% w/w — the declaration is available with the shipment documentation.