500 kW overload profile for pump and fan duty
The 6SL3220-2YE64-1CF0: Rated 500 kW with a 135% overload capability for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — this three-tier overload envelope matches the starting and transient demands of centrifugal pumps and axial fans in HVAC and water/wastewater networks. Input supply range is 3AC 380-480 V +10/-20% at 47-63 Hz, with an integrated RFI suppression filter for category C3 environments.
Active lifecycle and compliance documentation
RoHS compliant since 11-03-20; REACH Article 33 duty to inform applies for lead (CAS-No. 7439-92-1) at >0.1% w/w. Export control classification is AL N / ECCN EAR99H, requiring no special licensing for most destinations.
Panel integration and fieldbus connectivity
Size FSJ enclosure with IP20 / UL open type protection — mounts in a clean indoor panel; the open-type rating means it requires an enclosure for end-use compliance. A Basic Operator Panel and IO expansion are included, providing local control and additional I/O points without add-on hardware. Ambient temperature range is 0 to +45 °C; the drive must be derated or force-ventilated if installed above this ceiling.