560 kW at 380-480 V — what the overload ratings mean for pump and fan duty
The 6SL3220-2YE66-1CF0: Rated power is 560 kW with a 135% overload for 3 seconds or 110% for 60 seconds, 100% for 240 seconds — the 110% / 60 s window covers the starting current of a centrifugal pump or the stall torque of a fan at full speed, so you don't need to oversize the drive for transient loads.
Active production — no lifecycle risk for new builds
Lifecycle status is active, so this is a current-production Siemens drive — no last-time-buy clock ticking. The product class is C (manufactured to order), which means it's built per your BOM quantity, not held on a shelf; lead time and pricing are confirmed at RFQ.
Built for infrastructure: HVAC, water, wastewater
Part of the SINAMICS G120X family, purpose-built for infrastructure converters in HVAC, water, and wastewater applications. The RFI suppression filter is category C3 for 3AC 380-480 V +10/-20%, 47-63 Hz — meets the conducted emissions limits for industrial environments without an external filter.
Fieldbus and IO onboard — no extra modules for basic integration
Comes with PROFINET PN and Ethernet IP fieldbus integrated, plus an IO expansion module and a Basic Operator Panel. For a typical pump station or air handler, that's enough to get the drive talking to the PLC and running locally without ordering a separate comms card.
Compliance and export control
RoHS compliant since 11-03-20. REACH Article 33 duty to inform applies due to lead CAS-No. 7439-92-1 above 0.1% w/w. Export control classification is AL N / ECCN EAR99H — no special license required for most destinations, but confirm with your trade compliance team.