Skip to main content
Siemens 6SL3220-2YH56-1CB0 — AC Drives (VFD)

Siemens 6SL3220-2YH56-1CB0 SINAMICS G120X, 315 kW, 500-690 V

MPN6SL3220-2YH56-1CB0
Active

Siemens SINAMICS G120X infrastructure converter, 315 kW, 3AC 500-690 V, IP20 / UL open type, Size FSH, with Basic Operator Panel and IO expansion, MODBUS RTU, BACnet MS/TP, USS.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

6SL3220-2YH56-1CB0 — Identification
ParameterValue
Product familySINAMICS G120X infrastructure converters for HVAC/Water/Wastewater

Other specifications

6SL3220-2YH56-1CB0 — Other specifications
ParameterValue
Group codeR220
Product group4R53
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
Export control regulationsAL : N / ECCN : EAR99H
Compliance with the substance restrictions according to RoHS directiveSince: 11-03-20

Product details

315 kW at 500–690 V – overload profile for pump and fan loads

The 6SL3220-2YH56-1CB0: Rated power is 315 kW with an overload capability of 135 % for 3 s or 110 % for 60 s, 100 % for 240 s – the 110 %/60 s window covers the starting inrush of a centrifugal pump against a closed discharge valve without tripping on overcurrent. Input supply is 3AC 500–690 V +10/-20 %, 47–63 Hz, so it lands on a 575 V or 600 V plant distribution without a step-down transformer – confirm the line-side voltage matches the drive's nominal range before committing the BOM.

Fieldbus integration – MODBUS RTU and BACnet MS/TP on board

The drive ships with MODBUS RTU, BACnet MS/TP, and USS as standard – no option card needed for a BAS (building automation system) drop. The RS-485 termination and bias resistors are set at commissioning; a stray termination on a BACnet segment pulls the bus below the recessive threshold. The Basic Operator Panel (BOP) is included for local parameter access and fault diagnosis – useful during loop checks before the network handshake is live.

Size FSH, IP20 – panel layout and cooling

Packaged dimensions are 800 x 1,870 x 600 mm (L x W x H) – the FSH frame requires a backplate that clears the gland plate at the bottom and leaves 200 mm above for cable entry bend radius. IP20 / UL open type means the drive is not sealed against dust ingress; mount it inside a ventilated enclosure with a filter fan if the ambient is above 45 °C. Ambient temperature rating is 0 to +45 °C – derate output current above 40 °C per the SINAMICS G120X manual; the 315 kW figure assumes full cooling at 45 °C.

Active production – sourcing posture for this drive

The part is manufactured to order (product class C), so lead time and volume pricing are confirmed at RFQ against the specific BOM quantity. RoHS compliance date is 11-03-20; REACH Article 33 disclosure lists lead (CAS 7439-92-1) above 0.1 % w/w – the declaration is available with the shipment documentation.

MPN