Skip to main content
Siemens 6SL3220-2YH58-1CB0 — AC Drives (VFD)

Siemens 6SL3220-2YH58-1CB0 SINAMICS G120X, 355 kW, 500-690 V

MPN6SL3220-2YH58-1CB0
Active

Siemens SINAMICS G120X infrastructure converter, 355 kW, 500-690 V, 47-63 Hz, IP20, Size FSH, RFI filter C3, MODBUS RTU/BACnet MS/TP/USS.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

6SL3220-2YH58-1CB0 — Identification
ParameterValue
Product familySINAMICS G120X infrastructure converters for HVAC/Water/Wastewater

Other specifications

6SL3220-2YH58-1CB0 — Other specifications
ParameterValue
Group codeR220
Product group4R53
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
Export control regulationsAL : N / ECCN : EAR99H
Compliance with the substance restrictions according to RoHS directiveSince: 11-03-20

Product details

355 kW drive for HVAC and water infrastructure

The 6SL3220-2YH58-1CB0 is a SINAMICS G120X infrastructure converter rated 355 kW at 500-690 V, 47-63 Hz, designed for HVAC, water, and wastewater applications. It ships with a Basic Operator Panel, IO expansion, and integrated MODBUS RTU, BACnet MS/TP, and USS fieldbus. The FSH frame size and 800 x 1,870 x 600 mm packaging dimensions mean this is a large cabinet-mount drive — plan for a floor-standing enclosure or dedicated drive cabinet, not a panel retrofit.

Overload profile and duty cycle for pump/fan loads

Rated power is 355 kW with overload capability of 135% for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — this matches the typical starting and transient demands of centrifugal pumps and fans where high breakaway torque is brief and sustained overload is rare. The integrated RFI suppression filter is category C3 for 3AC 500-690 V, suitable for industrial environments with a dedicated transformer or IT supply. For residential or public low-voltage networks, an external C2 filter may be required depending on local EMC regulations.

Active production, quoted-to-order sourcing

Export control classification is AL N / ECCN EAR99H — no special license required for most destinations, but confirm end-use for high-tariff or sanctioned regions. RoHS compliant since 11-03-2020. REACH Art. 33 notification applies — the product contains lead (CAS 7439-92-1) above 0.1% w/w in certain components; this is standard for power electronics with soldered joints and does not affect normal installation or operation.

Frequently asked questions

What fieldbus protocols does this drive support?

Integrated fieldbus includes MODBUS RTU, BACnet MS/TP, and USS — covering the common building automation and water/wastewater communication standards out of the box without additional option modules.

What compliance documentation is available for this drive?

RoHS compliance effective 11-03-2020. REACH Art. 33 notification for lead content above 0.1% w/w (CAS 7439-92-1) is on file. Export control is AL N / ECCN EAR99H.

MPN
6SL3220-2YH58-1CB0